伊盾电气有限公司
IDBQY Dual Power Controller Series
Model number and meaning
Note: IDBQY-700 is configured with B, i and T functions, which shall be described separately
IDBQY-701 comes with B function
IDBQY-702 comes with T function
Standard: GB/T14048.11 IEC60947-6-1
IDBQY-700 dual power controller performance and features
The system type can be set as 128x64 LCD for 1 # mains power 2 # mains power, 1 # mains power 2 # power generation, 1 # mains power 2 # mains power, 1 # power 2 # power generation, with backlight in two languages (simplified Chinese and English display, touch the button for operation; collect and display two three-phase voltage and frequency parameters;
◇ It has the functions of overvoltage, undervoltage, phase loss, reverse phase sequence, overfrequency and underfrequency;
◇ It is equipped with automatic and manual state switching. Under manual mode, the closing and opening room can be forced to open
◇ Parameters can be programmed on site, and two-level password is used to prevent misoperation by non specialists
◇ On site, it can be set as the mode with load and without load for the commissioning operation of the generator set
◇ It has the function of switch reclosing and power off reclosing
◇ Closing output can be set as pulse or continuous output
◇ It can be applied to one breaking position, two breaking positions and no section position switch;
◇ Separation design of two N lines;
◇ Real time clock display
◇ It has the function of regularly starting and stopping the generator set, and can be set for single operation, once a month or once a week, and can be set for on load operation.
◇ It can control the cycle operation of two generator sets, and the operation time and interval shutdown time of generator sets can be set
◇ The range of DC power supply is extremely wide, which can withstand 80V DC input instantly, or through HWS560 (85V
◇ 560VAC input 12VDC output) power module power supply
◇ Large spacing of AC input terminals, which can withstand 625V voltage input;
◇ Equipped with RS-485 isolated communication interface and Modbus communication protocol, it has the "three remote" functions of remote control, remote signaling and telemetry, and can remotely control the startup, shutdown and ATS switching room of the generator set
◇ Current controller status can be queried (including internal switching values such as input port, overvoltage, undervoltage, etc.)
◇ Suitable for multiple connection types (three-phase four wire, three-phase three wire, single-phase two wire, two-phase three wire mode
◇ Modular structure design, flame-retardant ABS shell, pluggable terminal blocks, embedded installation mode, compact structure and convenient installation.
IDBQY-701/XLSY-702 controller function
Note: H = 003 when pressing the confirmation to restore the factory default value, please note that this will restore the original factory data, including the sampling coefficients of the common and standby power supply voltage, recovery may lead to the controller to collect voltage data with the actual standing input voltage difference of ± 10V or so.
Shape and mounting dimensions
8 building of Changhong Industrial Park, Huyang (Chating North Road), Liushi Town, Yueqing City, Zhejiang Province
期待你的来电